Key takeaways
Current capacity is not a property of a wire. It is the product of four conditions - conductor cross-section, insulation temperature class, ambient temperature with nearby heat sources, and bundling with routing. A supplier table maps to one fixed set of those conditions. Ambient derating and bundle derating add up, and several loaded circuits in the same bundle form a third heating path that is routinely missed. The conductor heats evenly while thermal resistance concentrates at the crimp interface and at branch points, so the hot spot sits at the terminal, not mid-run, and the criterion has to be temperature rise with the reference temperature stated. Current carrying is not steady state either: thermal cycling grows contact resistance, and heating and resistance push each other upward. Constant current will not expose that loop; on-off current cycling stacked with thermal cycling does.
How much current a wire can carry is not a lookup question. The number in a supplier table was measured under one fixed set of conditions - cross-section and material, insulation temperature class, ambient temperature, bundling and routing. Change any one of the four and the table value no longer transfers. What burns a harness is often not an undersized conductor but the temperature rise at the joint: the conductor heats evenly, while thermal resistance concentrates at the terminal.
The boundary first. This article covers only the current path through conductor and terminal, meaning how hot it gets once current flows and whether that heat is sustainable. Intermittent opens under vibration belong to a different line, covered in the harness vibration test discussion of fixing points and resonance search. Insulation that hardens or turns tacky is a materials ageing topic, treated separately under the two directions of insulation ageing.
1. Current capacity is four conditions multiplied
These are not four parallel parameters, they multiply. Shrink any one and the product shrinks. Yet when people read a table, they look at the cross-section column and stop there.
| Condition | What changes when it moves | Usually set by |
|---|---|---|
| --- | --- | --- |
| Cross-section and material | Higher resistance, more heat at the same current | Drawings and harness specification |
| Insulation temperature class | Caps the conductor temperature that is allowed | Material grade and OEM specification |
| Ambient temperature and nearby sources | Raises the starting point and eats the rise margin | Mounting location and neighbouring parts |
| Bundling and routing | Blocks the heat path, hotter at the same current | Routing design, tape and fixing |
So the question "how many amps will this cross-section take" actually reverses: under which conditions, and up to what temperature rise. Fix the conditions first and the current becomes meaningful.
2. Two derating routes add up, a third is routinely missed
In practice two steps get done: derate for ambient temperature, derate for bundling. The trouble is that these are treated as two independent options, take one factor each and stop.
| Derating source | How it acts | What happens when missed |
|---|---|---|
| --- | --- | --- |
| Ambient temperature | Higher starting point, less current for the same rise margin | Circuits in hot zones or near heat sources look optimistic |
| Bundling and taping | Adjacent wires heat each other, tape and sheath block the surface | Single-wire calculation passes, the bundle overheats |
| Several circuits loaded at once in one bundle | The number of heat sources doubles | Rated on a single circuit, the combined duty is ignored |
The third step is skipped most often because it needs a precondition: knowing which circuits run together on the vehicle. Headlamps, heaters, fans, pumps and charging are individually modest; switched on together they are a different case. On a request form this column usually reads "rated current", which carries no information at all.
3. The hot spot is not mid-run
A conductor heats evenly, and heat travels along the copper, so the rise along the conductor is gradual. Where thermal resistance concentrates is elsewhere.
| Location | Why it heats | How to measure |
|---|---|---|
| --- | --- | --- |
| Crimp interface between terminal and conductor | Effective contact area is smaller than the conductor section; contact resistance lives here | One point on the terminal body, one on the adjacent conductor, read the difference |
| Branches and splice points | Current redistributes, local density exceeds the trunk | Separate point, not shared with the mid-run |
| Grommets, sheath entries, tightly tied points | Dissipation is blocked by structure, tape or sheath | Measure each; design reviews skip these |
| Mid-run conductor | Reflects only the even heating of the conductor | Reference point, never a standalone criterion |
In one sentence: a normal mid-run reading does not mean the joint is normal. When a section of harness burns through, the records usually show a mild mid-run temperature all the way - the heat accumulated at the terminal, where nobody had placed a sensor.
4. The criterion is temperature rise, and the reference must be stated
Temperature rise is measured temperature minus reference temperature, so which reference you take decides whether the number is comparable at all. Chamber air, a neighbouring part, or the harness's own starting temperature will each give a different figure.
| Criterion form | What it answers | What it misses |
|---|---|---|
| --- | --- | --- |
| Absolute temperature | Whether insulation will soften or carbonise | How much thermal margin the joint retains |
| Rise against this run's reference | The heating level of this joint under load | Which other heat sources act outside the reference |
| Rise difference on the same part | How much the joint degraded across a test | Needs a comparable baseline |
The three are not interchangeable. Absolute temperature governs insulation; rise governs the connection. A report that states only an absolute temperature without its reference leaves the reader unable to judge the conditions behind the figure.
Steady state is the other place where wording gets loose. Steady state is not "reached a certain temperature", it is temperature no longer rising with time. Writing "record after stabilisation" without defining stabilisation and the observation window makes two labs' data impossible to compare.
5. Current carrying is not steady state: heat grows contact resistance
What actually destroys a harness is a positive feedback loop. Current flows and heats the joint; the thermal expansion mismatch between copper and terminal material relaxes contact pressure a little; contact resistance rises a little; the joint runs hotter; insulation starts to degrade and the terminal starts to anneal; resistance climbs again.
A constant-current run does not drive that loop. Temperature plateaus and stays there, the interface does not cycle, the chain never starts. On-off cycling forces it: every heat-up and cool-down is a load and an unload.
This is why current-carrying tests are often stacked with thermal cycling, and the reason is structural rather than a matter of being "stricter". Cold-state contact resistance also cannot show the hot state - contact resistance has to be measured once the joint is at steady state under load, or inferred from the rise in joint thermal resistance.
The four readings of a crimp cross-section examine interface quality itself; preload decay at grounding points examines a different family of joints coming loose. Both describe the same thing from different angles: degradation at a connection shows up in resistance first, and in temperature second.
6. Five columns in the plan, and what the report must show
| Column | What goes in it | Why it is often left blank |
|---|---|---|
| --- | --- | --- |
| Circuits and duty | Which circuits run together on the vehicle, in what combination | Reported per circuit while the reality is a bundle |
| Current and duty cycle | Constant, on-off cycling, ramps and short overloads | Only a rated current is filled in |
| Points and reference | What sits on terminal, branch and mid-run; which temperature is the reference | Chamber air assumed to be the reference |
| Criterion | Rise limit, before-and-after difference, appearance and insulation | Only "no smoke, no fire" |
| Records | Steady-state, ambient and load curves | One final-value photograph |
Among the five, points and reference is the column most often defaulted, and defaulting it makes data incomparable: measured twice with different results, nobody can say whether the part changed or the method did.
The report has to show the same items: where the points were, what the reference was, how steady state was judged, and which document the criterion comes from. GB/T 28046 and ISO 16750 supply the applied conditions and functional status grading for electrical and climatic loads; neither will compute how much current a given wire should carry. Current capacity and rise criteria come from the harness specification, material class and the customer technical agreement.
7. A few honest words
Calculate before testing. Writing the four conditions and two derating routes onto one page eliminates most circuits, and what remains is what genuinely needs a rig.
Change the terminal, change the crimp tooling or change the harness supplier, and the current-carrying conclusion has to be revisited - what changed is not the cross-section but the thermal resistance of that interface. Repeating everything is usually unnecessary; re-examining the terminal section is not.
When the rise margin is small, the first thing to move is not temperature but the contact resistance of the terminal. Watching the temperature and waiting for it to climb usually means waiting until the insulation discolours.
One more: never let a single-wire table value stand in for a bundle. A bundle's dissipation and a wire hanging in free air are not the same problem.
TMC LAB sets the circuit combination, measurement points, reference and criterion source into the test plan before any wiring is energised, and aligns the materials-side criteria for harnesses and connectors through its materials and processes service line. The testing itself is a routine item under environmental reliability, with conditions taken from the current edition of the relevant standard and the customer technical agreement.